Air source heat pump trouble shooting
Error
one: High pressure alarm and solution
High pressure alarm is the common error in the air source heat pump
system, there two types error in general, 1st is water piping
system, 2nd is the electrical system. The solution should be decided
after the error reason is clarified.
The error is because of electrical system if it alarms right after
the unit is energized and compressor is not started yet; the error is because
of water system, if the error comes after the unit runs for few minutes or a
while.
We can find the corresponding solution after the reason is
clarified.
I. Reason and solution for the HP alarm in
water system
It is more often to have HP alarm in water system, let’s explain it
first:
The 1st
situation: There is HP alarm within 3 to 5 minutes
after the unit is switched on, regardless the current water temperature, that
is to say, there is alarm right after the compressor start, the high pressure value
is higher than 3 MPa in the pressure gauge, it is mostly because of there is
block in the water circulation system.
The water level
in water tank should be checked first, then check the valve is open or not
before the water circulation pump, then check is the Y strainer (the Y strainer
stopper should downward, it should be noted during installation) blocked before
the water pump, then check is the air released in water pump, is the water pump
working normally or not? It is allowed, check the water circuit is normal or
not in the water tank. Most of the problem will be solved after the above steps
checked and corrected.
The 2nd
situation: The unit pressure is normal
when the water temperature is relatively low. There is HP alarm when the unit
runs for certain period or several hours, and the high pressure is higher than
3MPa. The main reasons are: water pump flow rate is not sufficient, circulation
pipe length is too long, or too many elbow, scale on heat exchanger.
The water pump
parameter is usually mentioned on the rating label of the unit, the pump should
be selected properly, if the pump is too small, the flow rate will be not
enough, it is easy to have HP alarm; there will be energy waste if the water
pump is selected too big. The circulation pipe between the unit and water tank,
distance no more than 3 meter, better to keep in 1.5 meter, and adopt 3 to 4
elbows (45℃).
If there are too
many elbow, the water resistance will be too big and water flow rate
insufficiency and HP alarm could be caused due to it. There is another reason
of HP alarm, scale in heat exchanger, if the water quality is poor, and calcium
and magnesium ions is much in water (TDS meter can check), the scale formation
is fast. Generally, if the TSD is above 200, the unit will have HP alarm after
operation of around 1 year.
If the HP alarm
is because of the scale, professional scale detergent should be used to clean
the heat exchanger. There are two ways of cleaning, one is to use interior
circulation that is suitable for the hot water system below 10 tons, another
one is exterior circulation that is suitable for hot water system above 10
tons. The dosage and period should be controlled well to avoid getting hole on
the heat exchanger.
For the small
hot water system, for example, below 10 tons, just keep the water level over
the circulation inlet/outlet, and put professional scale detergent or vinegar
into water tank and run the unit, to clean the unit and water piping. For the
bigger hot water system, the interior circulation method needs to drain huge
amount of the hot water in the water tank, it wastes water and time, so
exterior circulation method is recommended.
As shown in the picture above, steps as follow: Close the gate valve at the water circulation pipe to cut the circulation circuit, and add one water make up tunnel at the water inlet at the circulation water pump, and put the water outlet pipe of the unit inside the water make up tunnel, and put the professional detergent in the tunnel with water at the percentage specified in user manual, then run the unit and have circulation to clean the heat exchanger.
No matter which
cleaning method is used, how to know the cleaning result? For the interior
circulation method, we can observe the water temperature and high pressure
gauge during cleaning, when the water temperature is above 50 ℃ and the HP is below 2.5 MPa, it means
the heat exchanger is cleaned already. For exterior circulation, take the water
temperature sensor out of the water tank and put it in the water make up
tunnel, and observe the water temperature and high pressure gauge, when the
water temperature is 55℃ and pressure is below 2.5 MPa, it means the heat exchanger is
cleaned well.
Not to use
oxalic acid or diluted hydrochloric acid, for it is easy to get hole on the
heat exchanger and pipe due to strong corrosion.
II. Reason and solution for the HP alarm in
electrical system
1st
situation: If there is HP alarm right after pump is energized and no start of
pump, fan, compressor, mostly it is because of the failure of water tank temp.
sensor, high pressure switch or PCB.
Solution: First
check the water temperature displayed is the same as actual water temperature
or not, if the difference is too much, then replace the water temp. sensor.
There is one case happened, the displayed water temperature is 20 ℃, but the water is too hot from the water
tank, and the HP alarms after the unit is switched on. If the water temperature
displayed is same as actual water temp., then try to short connect the high
pressure switch at the PCB, and power on again to test, if there is no more
alarm, it means the high pressure switch is failed, if there is still alarm, it
means there is failure of the high pressure control chip in PCB. If it is high
pressure switch failure, then replace the coil of the high pressure switch, if
the problem is still there, then replace the high pressure switch from the
refrigerant circuit, and have the system vacuumed and charge refrigerant again.
2nd
situation: there is no regularity in the high pressure alarm, there is HP alarm
both in low water temp. period and high water temp. period, and the pressure
value is not high when there is HP alarm, it means the PCB should be replaced
due to the failure of HP chip in PCB.
Error
two: Low pressure alarm and solution
The are two situations for LP alarm.
1st
situation: There is LP alarm, and the LP displays normal when the unit is
running, and above 0.1MPa, it means the LP switch error or PCB error.
Inspection
method: Short connect the low pressure switch, and start the unit to test, if
the LP alarm still remains, then it is because of the PCB, if the LP alarm is
cleared, it means the LP switch is failed, inspection and replacement should be
done accordingly.
2nd
situation: There is LP alarm when the unit LP is below 0.1 MPa during unit
operation, it is because of refrigerant is not enough or no refrigerant.
Inspection
method: To check the leakage point and weld the leakage point well, then vacuum
it and charge refrigerant.
Error
three: Error of no water make up in water tank and its solution
For the air source heat pump water heater system, no water make up
is a common error, there are two reasons, one is pipe and water pressure,
another is the electrical control system error. Inspection method as below:
1.
If the water makeup does not
work when the water makeup valve is manually opened, the reason could be 1 water pressure is not enough. 2 water supply valve is closed or the valve is jammed 3 if there is floating ball in the water tank, it could be the
floating ball is jammed, and no makeup water can flow in.
2.
If it is the water makeup does
not work automatically, and it works with manual operation, the situation is
little more complicated, and can be classified as below:
1st situation, take out the water level sensor
all over the water surface, and the water makeup works with such enforced
action. The reasons are:
1 Water does not reach the temperature set for water makeup condition
( Normally the automatically water makeup water temperature is set at 50 ℃),water make up works by enforcement, taking all water level sensor
above water surface. The water is at certain water level in the tank, and the
water temperature does not reach the water makeup temp. setting, it does not
makeup the water.
2 There is scale on part of the water level sensor terminal, the
instrument does wrong code or wrong water level. The water makeup does not work
in such condition, which can work by enforcement, taking all water level sensor
out of the water surface, and the instrument shows no water. It is caused by
the scale on terminal.
2nd situation: There is no water makeup even the
water level sensor all over the water surface, the reasons are:
1 The instrument is in “OFF” status;
2 The solenoid valve core is jammed, or the solenoid valve coil
failed;
3 No power supply to the solenoid valve
If it is found there is no power supply to the solenoid
valve, then check the water makeup signal of the water level relay at the
control system of the unit, if the water level relay does not send the water
makeup signal, then it is because of the failure of the water level relay or
there is no output signal from the PCB, and the water level relay or the PCB
should be replaced.
Error
four: water tank overflow error and its solution
There are two
reasons for the water tank overflow in the air source heat pump hot water
system, one is the water piping error, another one is the electronic control
system error, the inspection method as below:
1.
There is water overflow even
the unit power is off, the reasons and solution as follow:
1 Check the manual water makeup valve is at “OPEN” status, then check
if there is a floating ball in the water tank, the floating ball is jammed or
not at the open status.
2 Check if the water pressure is too big, if the voltage is too high,
the solenoid valve spring can not get the membrane back at right position, and
water is not blocked.
3 then check if there is block at the membrane of water makeup
solenoid valve, and water can be held, or the valve core is blocked due to
scale when it is lifted, and not able to get back after power off.
4 If the water tank overflow is caused by continuous return water
from water return inlet, it could be there is block at the membrane of the
water return solenoid valve, and water can not be held, or the valve core is
blocked due to scale, and the indoor cold and hot water is connected or the
mixing valve core damaged, and water overflows due to the cold water get into
hot water pipe and enters the water tank through return water pipe.
A Y strainer must be fixed before the water inlet of water makeup
solenoid valve and return water solenoid valve, otherwise, it is easy to have
dirty or scale on the membrane and cause water overflow.
There is another special condition for the water overflow, the water
does not flow in through the cold water inlet, it gets in the water tank from
return water tank continuously, and the return water temp. does not rise, it
could be that the hot water and cold water pipe get connected or one mixing
valve core damaged at indoor, and the cold water gets into hot water pipe, and
flows into water tank through return water pipe and causes the water overflow.
The feature is that the water flow into water tank from return water pipe for
this problem.
There is one hot water system case, it is in a 50 rooms hotel in
tourist area, the tourist season is obvious, the occupation rate can be 100% in
peak season, and it is no more than 10% in off season (winter). 8 tons hot
water is selected. The user switch of the air source heat pump water heater is
switched off in off season, and install the electric water heater in room, as
the user though the power consumption is too high. It happens that there is hot
water in some room, and no hot water in some other room, and there is water
overflow from water tank in the peak season. It is found that the cold water
gets into the hot water pipe through electric heater, as the electric water
heater is not turned on in peak season, it is cold water in it, the it gets
into water tank through hot water pipe and causes water overflow. The solution
is to switch off the air source heat pump water heater in off season, and close
all the water inlet and outlet of the electric water heater in peak season.
2.
There is no water overflow when
the unit is power off, and there is overflow when the unit is energized, the
reason and solution as below:
1 The wrong water level signal is caused by the scale on the middle
and high water level terminal or the middle high water level sensor wire is
broken. The water overflow is caused by the continuous water makeup due to the
solenoid valve is always in power connected status by PCB or water level relay
and gives water lack signal even the water tank is already full.
2 There one more situation, the indoor cold water and hot water is
connected or the mixing valve core is damaged, and the cold water gets into hot
water pipe and enter the return water pipe, and the return water temperature
becomes lower, and the water return solenoid valve automatically open, and
causes the water overflow.
Error
five: evaporator frost and its solution
The heat pump water heater frost is common in winter, but if the
defrost can not be performed properly, the heating effect will be seriously
impacted, the inspection and solution as below:
First check the setting is correct or not, the defrost start time,
start temperature, defrost period, defrost stop temperature is reasonable or
not. The defrost start temperature is 2~4 ℃, defrost period is 30 to 45 minutes, and defrost stop temperature is
10 ℃ in general factory
setting. Inspect those setting is reasonable or not first, and then check the
next steps.
There are 8 situations of evaporator frost:
1.
Evaporator bottom part frost
It is mostly drainage is not smooth at drain pan, it will
be all right after the defrost manually with hot water and clean the dirty.
When there is frost on the evaporator, do not try remove the frost with hard
tool to avoid copper pipe damage or even refrigerant leakage. The best way is
to clean it with hot water.
2.
Equal frost on both side of
evaporator, and no defrost
1 Check the defrost temperature, or put the defrost sensor into
frost, it can be confirmed that the defrost sensor is failed if the defrost
temperature is above 5 ℃, then replace the defrost sensor after the defrost with hot water
flush.
2 If the compressor works normally, operate the reversing valve, or
directly energize the reversing valve, it can be confirmed that the reversing
valve coil is failed if there is no sound of pull in from the reversing valve,
and no sound of refrigerant flow; it is the reversing valve jammed if there is
sound of pull in but no sound of refrigerant flowing, and evaporator frosted,
then replace the reversing valve.
3.
Defrost can be performed when
there is frost, but defrost is not clean, not completely done, or there is
frost at one side and no frost at another side, the solution as follow:
1 The defrost stop temperature setting is too low or the defrost
period is too short, it will work after adjusting the defrost stop temperature
and defrost period accordingly.
2 The defrost sensor position is not reasonable, it will work after
placing the defrost sensor to the place with most serious frost.
4.
Frequent frost in short time
1 First inspect the defrost temperature is normal or not, if the
defrost temperature displays normal, in the condition of below 0 ℃, inspect the ventilation is good or not
around the unit, clean the object around the unit and flush the evaporator, and
reasonably extend the defrost time and increase the defrost stop temperature.
2 Frequent frost on the unit, and pressure is relatively low at
pressure gauge, defrost manually with hot water, and inspect the low pressure
gauge during heating, it is confirmed that the refrigerant is not sufficient or
refrigerant leaks if the pressure is lower than normal value (with reference of
similar unit).
3 The unit fan motor is damaged or the air flow rate is not enough,
for example, the fan blade is damaged or the fan motor power is relatively too
small.
5.
Frost on one side or two sides
frost is not equal or partial area frost on evaporator.
This situation is caused by the refrigerant is not equally
distributed, and mostly because of a certain pipe is blocked, the solution is
to move the defrost sensor to the place where it gets frost first and not easy
to defrost, or replace the copper tube and vacuum and charge refrigerant
accordingly.
6.
High pressure protection during
defrost process
This is because of the defrost stop temperature is set too
high, it will be all right after adjust it properly, and it is generally set at
10 ℃.
7.
Low pressure protection during
defrost process
This is caused by the block or the opening is too small
when the expansion valve flows reversely, the expansion valve should be
adjusted or replaced, please follow the specific adjustment method mentioned in
the manufacturer’s user manual, different model has different adjustment
parameter.
8.
It defrosts even no frost
This is because of the defrost start temperature setting is
too high or the defrost sensor is failed and causes wrong action, only needs to
adjust the defrost start temperature or replace the defrost sensor.
Q&A: High pressure alarm and
anti-freezing liquid etc.
1: Why the unit still works when there is
HP alarm with the unit?
A: There are two possibilities of this
problem, one is there is HP alarm on PCB, but no unit stop function interacted;
another one is the PCB, high pressure alarm and unit stop interaction chip is
failed, even there is high pressure alarm in instrument. The PCB should be
replaced regardless which situation it is.
2. The unit is just started, pump is
normal, and the high pressure gauge immediately rotates 180 degree, and have
high pressure alarm in a while, what is the problem?
A: It should be because of the air is not
released completely in the water pump, all the water pump should have air
released before operation.
3.
Heating with air source heat
pump, closed system, can the tap water pressure be directly used for water
makeup?
A: Yes, but make
sure the pressure is above 2 MPa.
4.
There is frost on from the
liquid distributor head to evaporator and evaporator part near the liquid
distribution pipe during the unit operation, why?
A: It should be
because of the liquid distribution is not equal, it is normal if there is
slight frost and can be defrosted, if the frost is heavy and it can not be
defrosted, it may because of the refrigerant is not enough or there is
refrigerant leakage.
5.
Should anti-freezing liquid be
used for the unit in Hebei area? And the percentage?
A: This should
be confirmed according to the local lowest ambient temperature in. The
percentage should be prepared according to the user manual, how many percent of
water, how many percent of anti-freezing liquid all described in the user
manual.
6.
There was a HP alarm, and I
clean the unit with oxalic acid, now it works well, should the PCB be replaced?
A: Not necessary
to replace the PCB now as it works well after cleaning with oxalic acid, and it
is not the problem of the PCB, it is because of the scale in heat exchanger,
and it is already cleaned.
It is better not
to use oxalic acid, it is strongly corrosive and slightly toxic. No matter what
type of detergent is used, the unit should be cleaned again with clean water
after the washing with detergent.
7.
What will happen if the air is
not released? Should air be released if there is no HP alarm?
A: It would
cause water flow rate insufficient if air was not released, even there was no
HP alarm, the unit operation pressure would be higher than that in standard
condition, and it’s more easier to have scale on heat exchanger.